Fully Automatic Oil / Gas / Electric Heated Mini Steam Generators - NANOMATIC

Features :

Gas fired Nanomatic - NM'G'

DETAILS UNITS NM'G' -35 NM'G'- 50 NM'G'-100
Steam Output Kgs/hr 35 50 100
Steam Pressure Kgs/cm² 5 5 5
Fuel
       
NG M3/hr 2.5 3.5 7.0
LPG Kgs/hr 2.0 2.6 5.2
Burnner Control ..............ON/OFF............
Efficiency %                        ..............88 ± 2. ...........
Electric Supply AC, 3 phase 415 V + 6%, 50 Hz, + 3 % 4 wire
System. (Single phase option also available)
Connected Elec. Load hp 0.2 0.2 0.2
Water Pump hp 1.0 1.0 1.0

Diesel Fired Nanomatic - NM'O'

DETAILS UNITS NM'O' -35 NM'O'- 50 NM'G'-100
Steam Output Kgs/hr 35 50 100
Steam Pressure Kgs/cm² 5 5 5
Fuel Consumption on full load, Cont operation basis
Ltrs/hr 2.75 3.6 7.2
Burner Control ..............ON/OFF............
Efficiency %                        ..............88 ± 2 ...........
Electric Supply AC, 3 phase 415 V + 6%, 50 Hz, + 3 % 4 wire
System. (Single phase option also available)
Connected Elec. Load hp 0.2 0.2 0.2
Water Pump hp 1.0 1.0 1.0

Electrically Heated Nanomatic - NM'E'

DETAILS UNITS NM'E' -14 NM'E'- 20 NM'E'-40
Steam Output Kgs/hr 14 20 40
Steam Pressure Kgs/cm² 5 5 5
Electrical Heated Load
KW 8 12 27
Operation ..............ON/OFF............
Electric Supply AC, 3 phase 415 V + 6%, 50 Hz, + 3 % 4 wire
System.
Connected Elec. Load hp 1.0 1.0 1.0
Water Pump        

'MINIMATIC'
MINI STEAM GENERATOR

Fully automatic Mini Steam Generator in Diesel Fired Design.


Neotech's Mini steam boiler Model 'Minimatic' is offerd in 4 sizes namely 50,100,150,& 200 Kgs/hr. These units are extremely efficient, because of 3-pass Deisgn and are fitted with imported world-class Monoblock Burner. These Boilers operate in vicinity of 90% efficiency & are instant steaming type. Due to this virtue, 'Minimatic' are very well accepted in the market and are ideal for replacing electrically heated Steam Boilers.

The unit is compact, skid mounted & incorporates numerous safety features for failsafe operation.

The control panel has audio visual alarm system giving clear cut idea of the faults.
Minimatic is available using Diesel or Gas as fuel.

TECHNICAL SPECIFICATIONS

DETAILS UNITS Minimatic - 50 Minimatic - 100 Minimatic - 150 Minimatic - 200
Steam Output (from & at 100°C) Kgs/hr 50 100 150 200
Steam Pressure Kgs/cm² 15 15 15 15
Fuel
  HSD/NG/LPG HSD/NG/LPG HSD/NG/LPG HSD/NG/LPG
Fuel Consumption
(on full load cont.
 operation basis)
HSD Ltrs/hr 3.6 7.2 10.8 14.4
 NG    Nm³/hr 3.5 7 10.5 14
LPG Kgs/hr 2.6 5.2 7.8 10.4
Start up Minutes ------------------ 3 ----------------
Burner Control
--------- ------------ ON - OFF -----------
Efficiency
% --------------- 88 +/-2% -----------
Pressure Parts
--------- ------------ Outside the purview of IBR -----------
Electric Supply
  AC-3 Phase - 415V+/-6%, 50Hz, 3Ø, 4 wire system
Connected Electric Load
Burner
Water Pump
hp
0.2
0.5

0.2
0.5

0.25
0.5

0.25
0.5
Flue gas outlet MM 150Ø 150Ø 200Ø 200Ø
Overall Dimensions         L   1.5 1.5 1.6 1.75
                                    W Mts 1.3 1.5 1.6 1.75
                                    H   1.5 1.6 1.6 1.6